State LEDs
LED State Color LED = OFF LED = ON
Inputs I0...I7 Digital input Yellow Input is OFF Input is ON
Outputs
O0...O7
Digital output Yellow Output is
OFF
Output is ON
Technical data
The System Data of AC500-eCo apply
Ä
Chapter 2.5.1 “System data AC500-eCo V3”
on page 925
Only additional details are therefore documented below.
Parameter Value
Process supply voltage UP
Connections Terminal 19 for UP (+24 V DC) and ter-
minal 20 for ZP (0 V DC)
Rated value 24 V DC
Current consumption via UP terminal 5 mA + max. 0.5 A per output
Max. ripple 5 %
Inrush current 0.000002 A²s
Protection against reversed voltage Yes
Rated protection fuse for UP Recommended; the outputs must be pro-
tected by an 3 A fast-acting fuse
Current consumption from 24 V DC power supply
at the L+/UP and M/ZP terminals of the CPU/com-
munication interface module
Ca. 10 mA
Galvanic isolation Yes, between the input group and the
output group and the rest of the module
Isolated groups 2 groups (1 group for 8 input channels, 1
group for 8 output channels)
Surge-voltage (max.) 35 V DC for 0.5 s
Max. power dissipation within the module 2.3 W
Weight ca. 120 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not
be hindered by cable ducts or other parts
in the switchgear cabinet.
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is
protected individually by an external fuse.
No effects of
multiple over-
loads
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US252