EasyManua.ls Logo

ABB AC500 V3 - Ordering data

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Galvanic isolation Against internal power supply and other modules
Input ranges Pt100, Pt1000, Ni100, Ni1000
150 W, 300 W
Indication of the input signals No
Module update time All channels: < 1 s
Channel input resistance > 100 kW
Input filter attenuation -3 dB at 3.6 kHz
Conversion error of the analog values
caused by non-linearity, adjustment
error at factory and resolution within
the normal range
Typ. Depending on RTD max. ±0.6 % of full scale
(guaranteed for 3-wires connection only)
at 25 °C
Max. ±2 % of full scale (guaranteed for 3-wires
connection only)
at 0 °C...60 °C or EMC disturbances
Measuring range
Ä
Chapter 1.6.2.1.2.8 “Measuring ranges”
on page 367
Analog to digital conversion time Typ. 140 ms per channel
Unused inputs Can be left open and should be configured as
"unused"
Input data length 4 bytes
Power dissipation inside the sensor
(max.)
1 mW
Suppression of interference On request
Maximum input voltage 30 V DC (sense), 5 V DC (source)
Basic error (resistance) 0.1 % of full-scale
Repeatability 0.05 % of full-scale
Overvoltage protection Yes, up to 30 V DC
Wire loop resistance < 20 W
Max. cable length (conductor cross
section > 0.14 mm²)
Unshielded wire 10 m
Shielded wire 100 m
Ordering data
Part no. Description Product life cycle phase *)
1TNE 968 902 R1102 AI562, analog input module, 2 AI, RTD Active
1TNE 968 901 R3102 Terminal block TA563-11, 11 pins,
screw front, cable side, 6 pieces per
unit
Active
Device specifications
I/O modules > Analog I/O modules
2022/01/313ADR010278, 3, en_US370

Table of Contents

Other manuals for ABB AC500 V3

Related product manuals