Channel parameters for the analog inputs (4x)
Name Value Internal value Internal value,
type
Default
Input 0, Channel
configuration
Table Operating
modes of the
analog inputs
Ä
Table 167 “Ch
annel configura-
tion”
on page 818
Table Operating
modes of the
analog inputs
Ä
Table 167 “Ch
annel configura-
tion”
on page 818
BYTE 0
Input 0, Check
channel
Table Channel
montoring
Ä
Table 168 “Ch
annel monitoring”
on page 819
Table Channel
montoring
Ä
Table 168 “Ch
annel monitoring”
on page 819
BYTE 0
: : : : :
: : : : :
Input 3, Channel
configuration
Table Operating
modes of the
analog inputs
Ä
Table 167 “Ch
annel configura-
tion”
on page 818
Table Operating
modes of the
analog inputs
Ä
Table 167 “Ch
annel configura-
tion”
on page 818
BYTE 0
Input 3, Check
channel
Table Channel
montoring
Ä
Table 168 “Ch
annel monitoring”
on page 819
Table Channel
montoring
Ä
Table 168 “Ch
annel monitoring”
on page 819
BYTE 0
Table 167: Channel configuration
Internal value Operating modes of the analog inputs, individually configurable
0 (default) Not used
1 0 V...10 V
2 Digital input
3 0 mA...20 mA
4 4 mA...20 mA
5 -10 V...+10 V
8 2-wire Pt100 -50 °C...+400 °C
9 3-wire Pt100 -50 °C...+400 °C *)
10 0 V...10 V (voltage diff.) *)
11 -10 V...+10 V (voltage diff.) *)
14 2-wire Pt100 -50 °C...+70 °C
15 3-wire Pt100 -50 °C...+70 °C *)
16 2-wire Pt1000 -50 °C...+400 °C
17 3-wire Pt1000 -50 °C...+400 °C *)
18 2-wire Ni1000 -50 °C...+150 °C
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/313ADR010278, 3, en_US818

Table of Contents