EasyManua.ls Logo

ABB AC500 V3 - 1.6.2.1.4 AO561 - Analog output module; Intended purpose

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.6.2.1.4 AO561 - Analog output module
2 configurable analog outputs (O0 and O1) in 1 group
Resolution: 11 bits plus sign or 12 bit
1 I/O bus
2 1 green LED to display power supply, 1 red LED to display error
3 Terminal number
4 Allocation of signal name
5 Terminal block for output signals (11-pin)
6 2 holes for wall-mounting with screws
7 DIN rail
Intended purpose
The device can be used as a decentralized I/O extension module for S500 communication
iInterface modules (e. g. CI592-CS31, CI501-PNIO, CI541-DP, CI581-CN) or as a centralized
extension module for AC500 CPUs.
The outputs are not galvanically isolated from each other.
The other electronic circuitry of the module is not galvanically isolated from the outputs or from
the I/O bus.
Device specifications
I/O modules > Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 383