Parameter Value
Conversion error of the analog values caused
by non-linearity, adjustment error at factory and
resolution within the normal range
Typ. 0.5 %, max. 1 %
For XC version below 0 °C and above 60 °C:
on request
Relationship between input signal and hex code
Ä
Chapter 1.6.3.1.1.9.1 “Input ranges
voltage, current and digital input”
on page 572
Ä
Chapter 1.6.3.1.1.9.2 “Input ranges resist-
ance temperature detector” on page 573
Unused inputs Are configured as "unused" (default value)
Overvoltage protection Yes
Technical data of the analog inputs, if used as digital inputs
Parameter Value
Number of channels per module Max. 4
Distribution of channels into groups 1 group of 4 channels
Connections of the channels AI0+ to AI3+ Terminals 3.0 to 3.3
Reference potential for the inputs Terminals 1.9, 2.9, 3.9 and 4.9 (ZP)
Indication of the input signals 1 LED per channel
Input signal voltage 24 V DC
Signal 0 -30 V...+5 V
Undefined signal +5 V...+13 V
Signal 1 +13 V...+30 V
Input current per channel
Input voltage +24 V Typ. 7 mA
Input voltage +5 V Typ. 1.4 mA
Input voltage +15 V Typ. 3.7 mA
Input voltage +30 V < 9 mA
Input resistance ca. 3.5 kW
Technical data of the analog outputs
Parameter Value
Number of channels per module 2
Distribution of channels into groups 1 group for 2 channels
Connection of the channels AO0+...AO1+ Terminals 3.5 and 3.6
Reference potential for AO0+ to AO1+ Terminal 3.7 (AO-) for voltage output
Terminals 1.9, 2.9, 3.9 and 4.9 for current
output
Output type
Unipolar Current
Bipolar Voltage
Device specifications
I/O modules > Digital/Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 581