EasyManua.ls Logo

ABB AC500 V3 - Parameterization; Input channel (4 x)

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameterization
The arrangement of the parameter data is performed with Automation Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Name Value Internal
Value
Internal
value,
Type
Default Min. Max. EDS Slot
Index
Module ID Intern
6500
1
)
WORD 0x1964 0 65535 xx01
Ignore
module
No
Yes
0
1
BYTE No
0x00
Parameter
length
Internal 6 BYTE 0 0 255
xx02
2
)
Check
Supply
Off
On
0
1
BYTE On
0x01
Analog
Data
Format
Default 0 BYTE Default
0x00
255
1
) with CS31 and addresses smaller than 70, the value is increased by 1
2
) Value is hexadecimal: HighByte is slot (xx: 0 ... 7), LowByte is index (1...n)
GSD file: Ext_User_Prm_Data_Len =
Ext_User_Prm_Data_Const(0
) =
0x09
0x65, 0x19, 0x06, \
0x01, 0x00, \
0x00, 0x00, 0x00, 0x00;
Input channel (4x)
Name Value Internal
value
Internal
value, Type
Default Min. Max.
Channel
configura-
tion
see table
2
) see table
2
)
BYTE 0
0x00
0 65535
Table 75: Channel configuration
2
)
Internal value Operating modes for the analog inputs, individu-
ally configurable
0 Not used (default)
1 0 V...10 V
3 0 mA...20 mA
4 4 mA...20 mA
6 0 V...5 V
Device specifications
I/O modules > Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 355

Table of Contents

Other manuals for ABB AC500 V3

Related product manuals