Parameter Value
With lamp loads 11 Hz max. at 5 W max.
Short-circuit-proof / overload-proof Yes
Overload message (I > 0.7 A) Yes, after ca. 100 ms
Output current limitation Yes, automatic reactivation after short cir-
cuit/overload
Resistance to feedback against 24 V signals Yes (software-controlled supervision)
Max. cable length
Shielded 1000 m
Unshielded 600 m
The following drawing shows the circuitry of a digital input/output with the varistors for demag-
netization when inductive loads are switched off.
Fig. 120: Digital input/output (circuit diagram)
1 Digital output
2 Varistors for demagnetization when inductive loads are turned off
Technical data of the configurable digital inputs/outputs
Each of the configurable I/O channels is defined as input or output by the user program. This is
done by interrogating or allocating the corresponding channel.
Parameter Value
Number of channels per module 8 inputs/outputs (with transistors)
Distribution of the channels into groups 1 group for 8 channels
If the channels are used as inputs
Channels DC0...DC07 Terminals 2.0...2.7
If the channels are used as outputs
Channels DC0...DC07 Terminals 2.0...2.7
Indication of the input/output signals 1 yellow LED per channel, the LED is ON
when the input/output signal is high (signal 1)
Galvanic isolation From the CANopen network
Communication interface modules (S500) > CANopen
2022/01/31 3ADR010278, 3, en_US 677