1
)
In AC500 the following interface identifier applies:
14 = I/O bus, 11 = COM1 (e.g. CS31 bus), 12 = COM2.
The PNIO diagnosis block does not contain this identifier.
2
)
With "Device" the following allocation applies:
31 = module itself, 1...10 = expansion module 1...10, ADR = hardware
address (e. g. of the DC551-CS31)
3
)
With "Module" the following allocation applies depending on the master:
Module error: I/O bus or PNIO: 31 = module itself; COM1/COM2: 1...10 =
expansion 1...10
Channel error: I/O bus or PNIO = module type (3 = AO); COM1/COM2:
1...10 = expansion 1...10
4
)
In case of module errors, with channel "31 = Module itself" is output.
State LEDs
LED State Color LED = OFF LED = ON LED flashes
PWR Process
voltage
24 V DC via
terminal
Green CPU module
voltage or
external
24 V DC
supply voltage
is missing
3.3 V system
voltage (I/O
bus) and
external
24 V DC supply
voltage are
present
---
ERR Channel or
module error
Red No error or
process
voltage is
missing
Severe error in
the module
Error on 1 or
more chan-
nels of the
module
Output ranges
Range -10 ... +10 V 0 ... 20 mA 4 ... 20 mA Digital value
Decimal Hex.
Overflow >11.7589 >23.5178 >22.8142 32767 7FFF
Value too high 11.7589
:
10.0058
:
:
23.5178
:
:
:
20.0058
22.8142
:
:
20.0058
:
32511
:
27664
27658
27656
7EFF
:
6C10
6C0A
6C08
Normal range
Normal range
or value too
low
10.0000
:
0.0058
:
:
20.0000
:
:
:
0.0058
20.0000
:
:
4.0058
27648
:
16
10
8
6C00
:
0010
000A
0008
0.0000 0 4 0 0000