Electromagnetic Compatibility
Digital inputs/outputs (100 V AC...240 V
AC)
Relay 2 kV
Ethernet 1 kV
Serial interfaces 1 kV
Immunity against the influence of line-con-
ducted interferences (CW conducted):
According to IEC 61000-4-6, zone B, crite-
rion A
Test voltage 10 V pass A
High energy surges According to IEC 61000-4-5, zone B, crite-
rion B
Power supply DC
1 kV CM / 0.5 kV DM
1
)
DC I/O supply
1 kV CM / 0.5 kV DM
1
)
Ethernet
1 kV CM
1
)
Serial interfaces
1 kV CM
1
)
AC I/O unshielded
2 kV CM, 1 kV DM
1
)
I/O analog, I/O DC unshielded
1 kV CM
1
)
Radiation (radio disturbance) According to IEC 55011, group 1, class A
1
) CM = Common Mode, DM = Differential Mode
2.5.1.5 Mechanical data
Parameter Value
Mounting Horizontal
Degree of protection EN61131-2: IP20 with all option boards or
option board slot covers attached (and all ter-
minal screws are tightened)
Housing Classification V0 according to UL 94
Vibration resistance acc. to EN 61131-2 all three axes (DIN rail mounting)
5 Hz...8.2 Hz: ±7.5 mm peak
8.2 Hz...150 Hz: 2 g peak
Shock test All three axes
15 g, 11 ms, half-sinusoidal
Mounting of the modules:
DIN rail according to DIN EN 50022 35 mm, depth 7.5 mm or 15 mm
Mounting with screws M3
Fastening torque 1.2 Nm
2.5.1.6 Approvals and certifications
Information on approvals and certificates can be found in the corresponding chapter of the Main
catalog, PLC Automation.