Range Pt100 / Pt1000
-50...+70 °C
Pt100 /
Pt1000
-50...400 °C
Ni1000
-50...150 °C
Digital value
Decimal Hex.
0.0 °C 0.0 °C 4000
1500
700
:
1
0FA0
05DC
02BC
:
0001
-0.1 °C
:
-50.0 °C
-0.1 °C
:
-50.0 °C
0 0000
Measured
value too
low
< -60.0 °C -50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-1
:
-500
FFFF
:
FE0C
Underflow < -60.0 °C < -60.0 °C < -60.0 °C -501
:
-600
FE0B
:
FDA8
Output ranges voltage and current
Range -10...+10 V 0...20 mA 4...20 mA Digital value
Decimal Hex.
Overflow > 11.7589 V > 23.5178
mA
> 22.8142
mA
> 32511 > 7EFF
Measured
value too
high
11.7589 V
:
10.0004 V
23.5178 mA
:
20.0007 mA
22.8142 mA
:
20.0006 mA
32511
:
27649
7EFF
:
6C01
Normal
range
10.0000 V
:
0.0004 V
20.0000 mA
:
0.0007 mA
20.0000 mA
:
4.0006 mA
27648
:
1
6C00
:
0001
0.0000 V 0.0000 mA 4.0000 mA 0 0000
-0.0004 V
:
-10.0000 V
0 mA
:
0 mA
3.9994 mA
0 mA
0 mA
-1
-6912
-27648
FFFF
E500
9400
Measured
value too low
-10.0004 V
:
-11.7589 V
0 mA
:
0 mA
0 mA
:
0 mA
-27649
:
-32512
93FF
:
8100
Underflow < -11.7589 V 0 mA 0 mA < -32512 < 8100
The represented resolution corresponds to 16 bits.