ABB AC500 V3 - 2.6.1.6 Mechanical data

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 200: Immunity against the influence of radiated (CW radiated), according to IEC
61000-4-3, zone B, criterion A
Parameter Value
Test field strength 10 V/m
Table 201: Immunity against fast transient interference voltages (burst), according to IEC
61000-4-4, zone B, criterion B
Parameter Value
Supply voltage units (DC) 2 kV
Supply voltage units (AC) 2 kV
Digital inputs/outputs (24 V DC) 1 kV
Digital inputs/outputs (120 V AC...240 V AC) 2 kV
Analog inputs/outputs 1 kV
CS31 bus 1 kV
Serial RS-485 interfaces (COM) 1 kV
Serial RS-232 interfaces (COM, not for PM55x
and PM56x)
1 kV
Ethernet 1 kV
I/O supply (DC-out) 1 kV
Table 202: Immunity against the influence of line-conducted interferences (CW conducted),
according to IEC 61000-4-6, zone B, criterion A
Parameter Value
Test voltage 3V zone B, 10 V is also met.
High energy surges According to IEC 61000-4-5, zone B, criterion
B
Power supply DC 1 kV CM / 0.5 kV DM ²)
DC I/O supply 0.5 kV CM / 0.5 kV DM ²)
Communication Lines, shielded 1 kV CM ²)
AC I/O unshielded
3
)
2 kV CM / 1 kV DM ²)
I/O analog, I/O DC unshielded
3
)
1 kV CM / 0.5 kV DM ²)
Radiation (radio disturbance) According to IEC 55011, group 1, class A
²) CM = Common Mode, DM = Differential Mode
3
) When DC I/O inputs are used with AC voltage, external filters limiting high energy surges to 1
kV CM / 0.5 DM are required to meet requirements according IEC 61131-2.
2.6.1.6 Mechanical data
Parameter Value
Mounting Horizontal
Degree of protection IP 20
Housing Classification V-2 according to UL 94
System assembly, construction and connection
AC500 (Standard) > System data AC500
2022/01/31 3ADR010278, 3, en_US 975