Parameterization
Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module: Module slot address: Y = 1...10
Name Value Internal value Internal
value, type
Default EDS Slot /
Index
Module ID
1
)
Internal 1810 WORD 1810 0x0Y01
Ignore module
see table
2
)
Internal Yes
No
BYTE No not for FBP
Parameter
length
Internal 8 BYTE 8 0xY02
Check supply off 0 BYTE 1 0xY03
on 1
Fast counter
3
)
0
:
10
4
)
0
:
10
BYTE 0 not for FBP
Behavior out-
puts at comm.
error
5
)
Off Last value
Last value 5
sec Last value
10 sec Substi-
tute value
Substitute
value 5 sec
Substitute
value 10 sec
0
1
6
11
2
7
12
BYTE Off
0x00
0x0Y07
2
)
Setting Description
On Error LED lights up at errors of all error classes, Failsafe
mode off
Off by E4 Error LED lights up at errors of error classes E1, E2 and E3,
Failsafe mode off
Off by E3 Error LED lights up at errors of error classes E1 and E2,
Failsafe mode off
On +Failsafe Error LED lights up at errors of all error classes, Failsafe
mode on *)
Device specifications
I/O modules > Digital/Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 565