Parameter Value
Signal 1 -30 V...-15 V +15 V...+30 V 14 V AC...27 V
AC
Input current per channel
Input voltage 24 V Typ. 5 mA Typ. 5 mA r.m.s.
Input voltage 5 V Typ. 1 mA Typ. 1 mA r.m.s.
Input voltage 14 V Typ. 2.7 mA r.m.s.
Input voltage 15 V > 2.5 mA
Input voltage 27 V Typ. 5.5 mA r.m.s.
Input voltage 30 V < 8 mA
Max. permissible leakage current (at 2-
wire proximity switches)
1 mA Typ. 1 mA r.m.s.
Input delay (0->1 or 1->0) Typ. 8 ms
Input data length 2 bytes
Max. cable length
Shielded 500 m
Unshielded 300 m
1
) When inputs are used with 24 V AC, external surge limiting filters are required.
Ordering data
Part no. Description Product life cycle phase *)
1TNE 968 902 R2102 DI562, digital input module, 16 DI,
24 V DC / 24 V AC
Active
1TNE 968 901 R3101 Terminal block TA563-9, 9 pins, screw
front, cable side, 6 pieces per unit
Active
1TNE 968 901 R3102 Terminal block TA563-11, 11 pins,
screw front, cable side, 6 pieces per
unit
Active
1TNE 968 901 R3103 Terminal block TA564-9, 9 pins, screw
front, cable front, 6 pieces per unit
Active
1TNE 968 901 R3104 Terminal block TA564-11, 11 pins,
screw front, cable front, 6 pieces per
unit
Active
1TNE 968 901 R3105 Terminal block TA565-9, 9 pins, spring
front, cable front, 6 pieces per unit
Active
1TNE 968 901 R3106 Terminal block TA565-11, 11 pins,
spring front, cable front, 6 pieces per
unit
Active
*) Modules in lifecycle Classic are available from stock but not recommended
for planning and commissioning of new installations.
Device specifications
I/O modules > Digital I/O modules
2022/01/31 3ADR010278, 3, en_US 175