Connection of DI561 - sink inputs Connection of DI561 - source inputs
The module provides several diagnosis functions
Ä
Chapter 1.6.1.1.3.6 “Diagnosis”
on page 165.
The meaning of the LEDs is described in the section State LEDs
Ä
Chapter 1.6.1.1.3.7 “State
LEDs” on page 166.
I/O Configuration
The module itself does not store configuration data. It receives its parameterization data from
the master device of the I/O bus (CPU or communication interface module) during power-up of
the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Parameterization
The arrangement of the parameter data is performed with Automation Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Name Value Internal
Value
Internal
Value,
Type
Default Min. Max. EDS Slot
Index
Module ID Internal
6105
1
)
WORD 6105
0x17D9
0 65535 xx01
Ignore
module
No
Yes
0
1
BYTE No (0x00)
Parameter
length
2
)
Internal 1 - CPU BYTE 0 0 255
xx02
3
)
1
) with CS31 and addresses smaller than 70, the value is increased by 1
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US164