Range 0...10 V -10...+10
V
0...20 mA 4...20 mA Digital
input
Digital value
Decimal Hex.
-0.0004
-1.7593
-0.0004
:
:
:
-10.0000
3.9994
:
0
-1
-4864
-6912
:
-27648
FFFF
ED00
E500
:
9400
Measured
value too
low
-10.0004
:
-11.7589
-27649
:
-32512
93FF
:
8100
Underflow <0.0000 <-11.7589 <0.0000 <0.0000 -32768 8000
Input ranges resistance temperature detector
Range Pt100 / Pt
1000
-50...70 °C
Pt100 /
Pt1000
-50...400 °C
Ni1000
-50...150 °C
Digital value
Decimal Hex.
Overflow > 80.0 °C > 450.0 °C > 160.0 °C 32767 7FFF
Measured
value too high
450.0 °C
:
400.1 °C
4500
:
4001
1194
:
0FA1
160.0 °C
:
150.1 °C
1600
:
1501
0640
:
05DD
80.0 °C
:
70.1 °C
800
:
701
0320
:
02BD
Normal range :
:
70.0 °C
:
0.1 °C
400.0 °C
:
:
:
0.1 °C
:
150.0 °C
:
:
0.1 °C
4000
1500
700
:
1
0FA0
05DC
02BC
:
0001
0.0 °C 0.0 °C 0.0 °C 0 0000
-0.1 °C
:
-50.0 °C
-0.1 °C
:
-50.0 °C
-0.1 °C
:
-50.0 °C
-1
:
-500
FFFF
:
FE0C
Measured
value too low
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-501
:
-600
FE0B
:
FDA8
Underflow < -60.0 °C < -60.0 °C < -60.0 °C -32768 8000
I/O modules > Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 427