Range 0...10 V -10...+10 V 0...20 mA 4...20 mA Digital input
Measured
value too low
-10.0004
:
-11.7589
Underflow < 0.0000 < -11.7589 < 0.0000 < 0.0000
Range Digital value
Decimal Hex.
Overflow 32767 7FFF
Measured value too high 32511
:
27649
7EFF
:
6C01
Normal range Normal range
or measured value too low
27648
:
1
6C00
:
0001
0 0000
-1
-4864
-6912
:
-27648
FFFF
ED00
E500
:
9400
Measured value too low -27649
:
-32512
93FF
:
8100
Underflow -32768 8000
The represented resolution corresponds to 16 bits.
Input ranges resistance temperature detector
Range Pt100 / Pt1000
-50...70 °C
Pt100 / Pt1000
-50...400 °C
Ni1000
-50...150 °C
Overflow > 80.0 °C > 450.0 °C > 160.0 °C
Measured value too high 450.0 °C
:
400.1 °C
160.0 °C
:
150.1 °C
80.0 °C
:
70.1 °C
Device specifications