NOTICE!
Risk of malfunctions in the plant!
The outputs may switch on for a period of 10 to 50 µs if the process supply
voltage UP/ZP is switched on.
This must be considered in the planning of the application.
NOTICE!
Risk of damaging the I/O module!
The outputs are not protected against short circuits and overload.
Never short-circuit or overload the outputs.
Never connect the outputs to other voltages.
Use an external 3 A fast-protection fuse for the outputs.
The module provides several diagnosis functions (see Diagnosis
Ä
Chapter 1.6.1.1.7.6 “Diag-
nosis” on page 198).
The meaning of the LEDs is described in the section State LEDs
Ä
Chapter 1.6.1.1.7.7 “State
LEDs” on page 199.
I/O configuration
The module itself does not store configuration data. It receives its parameterization data from
the master device of the I/O bus (CPU or communication interface module) during power-up of
the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
Device specifications
I/O modules > Digital I/O modules
2022/01/31 3ADR010278, 3, en_US 197