EasyManua.ls Logo

ABB AC500 V3 - Technical data of the digital inputs

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
Parameter Value
Bus connection 2 x RJ45
Switch Integrated
Technology Hilscher NETX 100
Transfer rate 10/100 Mbit/s (full-duplex)
Transfer method According to Ethernet II, IEEE 802.3
Ethernet 100 base-TX, internal switch, 2x RJ45 socket
Expandability Max. 10 S500 I/O modules
Adjusting elements 2 rotary switches for generation of an explicit
name
Supported protocols RTC - real time cyclic protocol, class 1 *)
RTA - real time acyclic protocol
DCP - discovery and configuration protocol
CL-RPC - connectionless remote procedure
Call
LLDP - link layer discovery protocol
MRP - MRP Client
Acyclic services PNIO read / write sequence (max. 1024 bytes
per telegram)
Process-Alarm service
Supported alarm types Process Alarm, Diagnostic Alarm, Return of
SubModule, Plug Alarm, Pull Alarm
Min. bus cycle 1 ms
Conformance class CC A
Protective functions (according to
IEC 61131-3)
Protected against:
short circuit
reverse supply
overvoltage
reverse polarity
Galvanic isolation from the rest of the module
*) Priorization with the aid of VLAN-ID including priority level
Technical data of the digital inputs
Parameter Value
Number of channels per module 8
Distribution of the channels into groups 1 group of 8 channels
Terminals of the channels DI0 to DI7 Terminals 2.0 to 2.7
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/313ADR010278, 3, en_US856