State LEDs
LED State Color LED = OFF LED = ON
Inputs I0...I7 Digital input Yellow Input is OFF Input is ON
In the undefined signal range, the state LED for the inputs can be ON although
the input state detected by the module is OFF.
Technical data
The System Data of AC500-eCo apply
Ä
Chapter 2.5.1 “System data AC500-eCo V3”
on page 925
Only additional details are therefore documented below.
Parameter Value
Galvanic isolation Yes, between the input group and the rest of
the module
Isolated groups 1 (8 channels per group)
Current consumption from 24 V DC power
supply at the L+/UP and M/ZP terminals of
the CPU/communication interface module
Ca. 10 mA
Max. power dissipation within the module 1.6 W
Weight Ca. 110 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
Technical data of the digital inputs
Parameter Value
Number of channels per module 8 inputs (24 V DC / 24 V AC)
Distribution of the channels into
groups
1 (8 channels per group)
Connections of the channels I0 to I7 Terminals 2 to 9
Reference potential for the channels
I0 to I7
Terminal 1 (plus or negative pole of the process supply
voltage, signal name C0..7)
Indication of the input signals 1 yellow LED per channel; the LED is ON when the
input signal is high (signal 1). The module is powered
through the I/O bus.
Monitoring point of input indicator LED is part of the input circuitry
Input type according to EN 61131-2 Type 1 source Type 1 sink
Type 1 AC
1
)
Device specifications
I/O modules > Digital I/O modules