LED Color OFF ON Flashing
UP3 Green Process supply
voltage missing
Process supply
voltage OK
--
CH-ERR1 to CH-
ERR3
Red No error or
process supply
voltage missing
Internal error Error on one
channel of the
corresponding
group
1.7.2.2.10 Measuring ranges
Input ranges voltage, current and digital input
Range 0...10 V -10...+10
V
0...20 mA 4...20 mA Digital
input
Digital value
Decimal Hex.
Overflow >11.7589 >11.7589 >23.5178 >22.8142 32767 7FFF
Measured
value too
high
11.7589
:
10.0004
11.7589
:
10.0004
23.5178
:
20.0007
22.8142
:
20.0006
32511
:
27649
7EFF
: 6C01
Normal
range
Normal
range or
measured
value too
low
10.0000
:
0.0004
10.0000
:
0.0004
20.0000
:
0.0007
20.0000
:
4.0006
:
:
On
27648
:
1
6C00
:
0001
0.0000 0.0000 0 4 Off 0 0000
-0.0004
-1.7593
-0.0004
:
:
:
-10,0000
3.9994
:
0
-1
-4864
-6912
:
-27648
FFFF
ED00
E500
:
9400
Measured
value too
low
-10.0004
:
-11.7589
-27649
:
-32512
93FF
: 8100
Underflow <0.0000 <-11.7589 <0.0000 <0.0000 -32768 8000
The represented resolution corresponds to 16 bits.
Input ranges resistance temperature detector
Range Pt100 / Pt1000
-50...400 °C
Ni1000
-50...150 °C
Digital value
Decimal Hex.
Overflow > 450.0 °C > 160.0 °C 32767 7FFF
Measured value
too high
450.0 °C
:
400.1 °C
4500
:
4001
1194
:
0FA1
Device specifications
Communication interface modules (S500) > CANopen
2022/01/313ADR010278, 3, en_US650