ABB AC500 V3 - 1.7.2.2.9 State LEDs

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
)
In AC500, the following interface identifier applies:
"-" = Diagnosis via bus-specific function blocks; 0 ... 4 or 10 = position of the
communication module;14 = I/O bus; 31 = module itself
The identifier is not contained in the CI541-DP diagnosis block.
2
)
With "Device" the following allocation applies: 31 = module itself; 1..10 = decen-
tralized communication interface module
3
)
With "Module" the following allocation applies:
31 = module itself
Channel error: module type (1 = AI, 2 = DO, 3 = AO)
4
)
This message appears if external voltages at one or more terminals DO0..DO7
cause other digital outputs to be fed by that voltage (voltage feedback, descrip-
tion in 'Connections'
Ä
Chapter 1.7.2.2.3 “Connections” on page 623). All out-
puts of the digital output groups will be turned off for 5 seconds. The diagnosis
message appears for the whole output group.
5
)
The voltage on digital outputs DO0..DO7 has overrun the process supply
voltage UP3 (description in 'Connections'
Ä
Chapter 1.7.2.2.3 “Connections”
on page 623). Diagnosis message appears for the whole module.
6
)
This message appears if the output of a channel DO0..DO7 is to be switched
on while an external voltage is connected. In this case, start-up is disabled while
the external voltage is connected. Otherwise, this could produce reverse voltage
flowing from this output to other digital outputs. This diagnosis message appears
for each channel.
7
)
Short circuit: After a short circuit has been detected, the output is deactivated for
100ms seconds. Subsequently, a new start-up will be executed. This diagnosis
message appears for each channel.
1.7.2.2.9 State LEDs
The state LEDs are located at the front of module. There are 2 different groups:
The 5 system LEDs (PWR, CN-RUN, CN-ERR, S-ERR and I/O bus) show the operation
states of the module and display possible errors.
The 27 process LEDs (UP, UP3, inputs, outputs, CH-ERR1 to CH-ERR3) show the process
supply voltage and the states of the inputs and outputs and display possible errors.
LED Color OFF ON Flashing
PWR/RUN Green Process supply
voltage missing
Internal supply
voltage OK,
module ready for
communication
with I/O controller
Start-up / pre-
paring communi-
cation
Yellow --- --- ---
States of the 5
system LEDs
Device specifications
Communication interface modules (S500) > CANopen
2022/01/313ADR010278, 3, en_US648