Parameter Value
Inrush current from UP3 or UP4 (at
power up)
0.005 A²s (without output load)
Max. power dissipation within the module 6 W
Weight (without terminal unit) Ca. 135 g
Mounting position Horizontal
Or vertical with derating (output load reduced to
50 % at 40 °C per group)
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply and continuous overvoltage up to 30 V DC.
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is
protected individually by an external fuse.
Technical data of the digital outputs
Parameter Value
Number of channels per module 8 outputs (with transistors, non-latching type)
Distribution of the channels into groups 2 groups of 4 channels
Connection of the channels
O0 to O3 Terminals 3.0, 3.1, 3.4, 3.5
O4 to O7 Terminals 4.0, 4.1, 4.4, 4.5
Indication of the output signals 1 yellow LED per channel, the LED is ON if the
output signal is high (signal 1)
Power supply voltage for the module Terminals 1.8 and 2.8 (positive pole of the
process supply voltage, signal name UP)
Reference potential for module power supply Terminals 1.9 and 2.9 (negative pole of the
process supply voltage, signal name ZP)
Power supply voltage for the outputs O0 to
O3
Terminal 3.8 (positive pole of the process
supply voltage, signal name UP3)
Reference potential for the outputs O0 to O3 Terminal 3.9 (negative pole of the process
supply voltage, signal name ZP3)
Power supply voltage for the outputs O4 to
O7
Terminal 4.8 (positive pole of the process
supply voltage, signal name UP4)
Reference potential for the outputs O4 to O7 Terminal 4.9 (negative pole of the process
supply voltage, signal name ZP4)
Output voltage for signal 1 UP (-0.4 V)
Output delay (0->1 or 1->0) On request
Output current
Rated value, per channel 2 A at UP3 or UP4 = 24 V
No effects of
multiple over-
loads
Device specifications
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US326