Functionality
2 analog RTD-inputs, individually configurable for
● Not used (default)
● Pt100, -50 °C...+400 °C, 2-wire
● Pt100, -50 °C...+400 °C, 3-wire
● Pt1000, -50 °C...+400 °C, 2-wire
● Pt1000, -50 °C...+400 °C, 3-wire
● Ni1000, -50 °C...+150 °C, 2-wire
● Ni1000, -50 °C...+150 °C, 3-wire
● Ni100, -50 °C...+150 °C, 2-wire
● Ni100, -50 °C...+150 °C, 3-wire
● Analog input resistance 0 W...150 W
● Analog input resistance 0 W...300 W
Parameter Value
Resolution of the analog channels
Temperature 0.1 °C
LED displays 2 LEDs for process voltage and error messages
Internal supply Via I/O bus
External supply Via the terminals UP (process voltage 24 V DC) and
ZP (0 V DC)
Connections
For a detailed description of the mounting, disassembly and connection of the
module, please refer to the System Assembly chapter
Ä
Chapter 2.5 “AC500-
eCo” on page 925.
The connection is carried out by using a removable 9-pin and 11-pin terminal block. These
terminal blocks differ in their connection system (spring terminals or screw terminals, cable
mounting from the front or from the side). The terminal blocks are not included in the module's
scope of delivery and must be ordered separately.
The following block diagram shows the internal construction of the analog inputs:
I/O modules > Analog I/O modules
2022/01/313ADR010278, 3, en_US362