EasyManua.ls Logo

ABB AC500 V3 - Resistor input range; Thermocouple input ranges

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Range Pt100
-50 ...
+70 °C
1
)
Pt100 /
Pt1000
-50 ...
+400 °C
Pt100
-200 ...
+850 °C
Ni1000
-50 ...
+150 °C
Cu50
-200 ...
+200 °C
Digital value
Decimal Hex.
Measured
value too
low
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-501
:
-600
FE0B
:
FDA8
Under-
flow
< -60.0
°C
< -60.0
°C
< -200 °C < -60.0
°C
< -200 °C
2
)
-32768 8000
1
) also possible with resolution 0.01 K
2
) if Cu50 with 1.426, -50 °C is valid; if Cu50 with 1.428, -200.0 °C is valid
Resistor input range
The represented resolution corresponds to 16 bits.
Range Resistor [W] Digital value
Decimal Hex.
Overflow > 55000 32767 7FFF
Measured value
too high
55000
:
50001
30413
:
27649
76CD
:
6C01
Normal range 50000
:
2
1
0
27648
:
1
1
0
6C00
:
0001
0001
0000
Thermocouple input ranges
The represented resolution corresponds to 16 bits.
Range Typ J
-210 ...
+1200 °C
Typ K
-270 ...
+1372 °C
Typ N
-270 ...
+1300 °C
Typ S
-50 ...
+1768 °C
Typ T
-270 ...
+400 °C
Digital value
Decimal Hex.
Overflow > 1200.0
°C
> 1372.0
°C
> 1300.0
°C
> 1768.0
°C
> 400.0
°C
32767 7FFF
Normal
range
1768.0 °C 17680 4510
1372.0 °C : 13720 3598
: 1300.0 °C : 13000 32C8
1200.0 °C : : : 12000 2EE0
: : : : 400.0 °C 4000 0FA0
: : : : : : :
Device specifications
I/O modules > Analog I/O modules