Internal data exchange
Digital inputs (bytes) 0
Digital outputs (bytes) 0
Analog inputs (words) 8
Analog outputs (words) 1
I/O configuration
The module does not store configuration data itself. It gets its parameterization data from the
master device of the I/O bus (CPU or communication interface module) during power-up of the
system.
This means that replacing I/O modules is possible without any re-parameterization via software.
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Parameterization
Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module: Module slot address: Y = 1...10
Name Value Internal
value
Internal
value,
Type
Default Min. Max. EDS Slot/
Index
Module ID Internal 1535
1
)
Word 1535
0x05ff
0 65535 0x0Y01
Ignore
module
2
)
No
Yes
0
1
Byte No
0x00
Not for
FBP
Parameter
length in
bytes
Internal 36 Byte 36 0 255 0x0Y02
Check
supply
Off
On
0
1
Byte On
0x01
0x0Y03
Analog
data
format
Default 0 Byte Default
0x00
0x0Y04
1
) With CS31 and addresses smaller than 70 and FBP, the value is increased by 1
Device specifications
I/O modules > Analog I/O modules
2022/01/313ADR010278, 3, en_US472