ABB AC500 V3 - Connection of passive-type analog sensors (Current)

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
0...10 V
AGND
1.0
1.1
1.8
1.9
AI0+
AI1+
UP
ZP
UP
ZP
PTC
1.5
AI–
UP (remote)
ZP (remote)
1
2
3
Fig. 127: Connection of active-type sensors (voltage) with no galvanically isolated power supply
1 1 analog sensor requires 1 channel
2 Power supply not galvanically isolated
3 The connection between the negative pole of the sensor and ZP has to be performed
4 Long cable
NOTICE!
Risk of faulty measurements!
The negative pole/ground potential at the sensors must not have too large a
potential difference with respect to ZP (max. ± 1 V within the full signal range).
Make sure that the potential difference never exceeds ± 1 V.
Voltage 0...10 V 1 channel used
Voltage -10 V...+10 V *) 1 channel used
*) if the sensor can provide this signal range
The measuring ranges are described in the section Measuring Ranges
Ä
Chapter 1.7.3.1.7
“Parameterization” on page 694
Ä
Chapter 1.7.3.1.10 “Measuring ranges” on page 703.
In order to avoid error messages or long processing times, it is useful to configure unused
analog input channels as "unused".
Connection of passive-type analog sensors (Current)
The following figure shows the connection of passive-type analog sensors (current).
Device specifications
Communication interface modules (S500) > EtherCAT
2022/01/313ADR010278, 3, en_US688