NOTICE!
Risk of malfunctions!
Unused slots for communication modules are not protected against accidental
physical contact.
– Unused slots for communication modules must be covered with dummy
communication modules to achieve IP20 rating
Ä
Chapter 2.6.5.6 “TA524 -
Dummy communication module” on page 1019.
– I/O bus connectors must not be touched during operation.
2.7.1.2 Mechanical data
Parameter Value
Wiring method Spring terminals
Degree of protection IP 20
Vibration resistance Yes, according to:
IEC 61131-2
IEC 60068-2-6
IEC 60068-2-64
Shock resistance Yes, according to:
IEC 60068-2-27
Assembly position Horizontal
Vertical (no application in salt mist environ-
ment)
Assembly on DIN rail
DIN rail type According to IEC 60715
35 mm, depth 7.5 mm or 15 mm
Assembly with screws
Screw diameter 4 mm
Fastening torque 1.2 Nm
2.7.1.3 Environmental tests
Parameter Value
Storage IEC 60068-2-1 Test Ab: cold withstand test -40 °C / 16 h
IEC 60068-2-2 Test Bb: dry heat withstand test +85 °C / 16 h
Humidity IEC 60068-2-30 Test Db: Cyclic (12 h / 12 h) damp-heat test
55 °C, 93 % r. H. / 25 °C, 95 % r. H., 6 cycles
IEC 60068-2-78, stationary humidity test: 40 °C, 93 % r. H.,
240 h
Insulation Test IEC 61131-2
System assembly, construction and connection
AC500-XC > System data AC500-XC