Parameter Value
Max. power dissipation within the module 6 W (outputs unloaded)
Sensor power supply
Connections Terminals 1.0...1.3 = +24 V, 1.4...1.7 = 0 V
Terminals 3.0...3.3 = +24 V, 3.4...3.7 = 0 V
Voltage 24 V DC with short-circuit and overload protec-
tion
Loadability Terminals 1.0...1.3, in total max. 0.5 A
Terminals 3.0...3.3, in total max. 0.5 A
Weight (without terminal unit) Ca. 125 g
Mounting position Horizontal
Or vertical with derating (output load reduced to
50 % at 40 °C per group)
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
Technical data of the configurable digital inputs/outputs
Each of the configurable I/O channels is defined as input or output by the user program. This is
done by interrogating or allocating the corresponding channel.
Parameter Value
Number of channels per module 16 inputs/outputs (with transistors)
Distribution of the channels into groups 1 group of 16 channels
If the channels are used as inputs
Channels C0...C7 Terminals 2.0...2.7
Channels C8...C15 Terminals 4.0...4.7
If the channels are used as outputs
Channels C0...C7 Terminals 2.0...2.7
Channels C8 C15 Terminals 4.0...4.7
Indication of the input/output signals 1 yellow LED per channel, the LED is ON
when the input/output signal is high (signal 1)
Device specifications
I/O modules > Digital I/O modules