EasyManua.ls Logo

ABB AC500 V3 - Input ranges resistance temperature detector

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Range 0...10 V -10...+10
V
0...20 mA 4...20 mA Digital
input
Digital value
Decimal Hex.
Measured
value too
low
-10.0004
:
-11.7589
-27649
:
-32512
93FF
:
8100
Underflow <0.0000 <-11.7589 <0.0000 <0.0000 -32768 8000
The represented resolution corresponds to 16 bits.
Input ranges resistance temperature detector
Range Pt100 /
Pt1000
-50...70 °C
Pt100 / Pt1000
-50...400 °C
Ni1000
-50...150 °C
Digital value
Decimal Hex.
Overflow > 80.0 °C > 450.0 °C > 160.0 °C 32767 7FFF
Measured
value too
high
450.0 °C
:
400.1 °C
4500
:
4001
1194
:
0FA1
160.0 °C
:
150.1 °C
1600
:
1501
0640
:
05DD
80.0 °C
:
70.1 °C
800
:
701
0320
:
02BD
Normal range 70.0 °C
:
0.1 °C
400.0 °C
:
:
:
0.1 °C
150.0 °C
:
:
0.1 °C
4000
1500
700
:
1
0FA0
05DC
02BC
:
0001
0.0 °C 0.0 °C 0.0 °C 0 0000
Normal range -0.1 °C
:
-50.0 °C
-0.1 °C
:
-50.0 °C
-0.1 °C
:
-50,0 °C
-1
:
-500
FFFF
:
FE0C
Measured
value too low
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-501
:
-600
FE0B
:
FDA8
Underflow < -60.0 °C < -60.0 °C < -60.0 °C -32768 8000
Device specifications
Communication interface modules (S500) > Modbus
2022/01/313ADR010278, 3, en_US762