Diagnosis
E1...E4 d1 d2 d3 d4 Identifier
000...063
AC500-
Display
<− Display in
Class Comp Dev Mod Ch Err PS501
PLC
Browser
Byte 6
Bit 6...7
- Byte 3 Byte 4 Byte 5 Byte 6
Bit 0...5
PNIO
diagnosis
block
Class Interface Device Module Channel Error
Identifier
Error message Remedy
1
)
2
)
3
)
4
)
Module error DI571
3 14 1...10 31 31 19 Checksum error in the
I/O module
Replace
I/O module
11 / 12 ADR 1...10
3 14 1...10 31 31 43 Internal error in the
module
Replace
I/O module
11 / 12 ADR 1...10
3 14 1...10 31 31 9 Overflow diagnosis
buffer
Restart
11 / 12 ADR 1...10
3 14 1...10 31 31 26 Parameter error Check
master
11 / 12 ADR 1...10
Remarks:
1
)
In AC500 the following interface identifier applies:
14 = I/O bus, 11 = COM1 (e.g. CS31 bus), 12 = COM2.
The PNIO diagnosis block does not contain this identifier.
2
)
With "Device" the following allocation applies:
31 = module itself, 1...10 = decentralized communication interface module
1...10, ADR = hardware address (e. g. of the DC551-CS31)
3
)
With "Module" the following allocation applies depending on the master:
Module error: I/O bus or PNIO: 31 = module itself; COM1/COM2: 1...10 =
expansion 1...10
4
)
In case of module errors, with channel "31 = Module itself" is output.
State LEDs
LED State Color LED = OFF LED = ON
Inputs/outputs
C0...C15
Digital input
or
digital output
Yellow Input/output
is OFF
Input/output is ON
(the LEDs are only
operating if the
module's circuitry is
supplied via the
I/O bus)
Device specifications
I/O modules > Digital I/O modules
2022/01/31 3ADR010278, 3, en_US 147