Technical data
The system data of AC500 and S500
Ä
Chapter 2.6.1 “System data AC500” on page 971 are
applicable to the standard version.
The system data of AC500-XC
Ä
Chapter 2.7.1 “System data AC500-XC” on page 1023 are
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter Value
Process voltage
Connections Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V
(UP) as well as 1.9, 2.9, 3.9 and 4.9 for
0 V (ZP)
Rated value 24 V DC
Max. ripple 5 %
Protection against reversed voltage Yes
Rated protection fuse on UP 10 A fast
Galvanic isolation Yes, per module
Current consumption
From 24 V DC power supply at the terminals
UP/L+ and ZP/M of the CPU/communication
interface module
Ca. 2 mA
Current consumption from UP at normal oper-
ation
0.15 A + output loads
Inrush current from UP (at power up)
0.040 A
2
s
Max. length of analog cables, conductor cross sec-
tion > 0.14 mm
2
100 m
Weight 300 g
Mounting position Horizontal or vertical with derating
(output load reduced to 50 % at 40 °C
per group)
Cooling The natural convection cooling must not
be hindered by cable ducts or other
parts in the switchgear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.