Parameter Value
Vibration resistance acc. to EN 61131-2 all three axes
2 Hz...8.4 Hz, continuous 3.5 mm
8.4 Hz...150 Hz, continuous 1 g (higher values
on request)
Shock test All three axes
15 g, 11 ms, half-sinusoidal
Mounting of the modules:
DIN rail according to DIN EN 50022 35 mm, depth 7.5 mm or 15 mm
Mounting with screws Screws with a diameter of 4 mm
Fastening torque 1.2 Nm
2.6.1.7 Approvals and certifications
Information on approvals and certificates can be found in the corresponding chapter of the Main
catalog, PLC Automation.
2.6.2 Mechanical dimensions
2.6.2.1 Switchgear cabinet assembly
Information on EMC-conforming assembly and construction is provided within
the overall functions section
Ä
Chapter 2.4.4 “EMC-conforming assembly and
construction” on page 918.
NOTICE!
PLC damage due to wrong enclosures
Due to their construction (degree of protection IP 20 according to EN 60529)
and their connection technology, the devices are suitable only for operation in
enclosed switchgear cabinets.
To protect PLCs against:
unauthorized access,
dusting and pollution,
moisture and wetness and
mechanical damage,
switchgear cabinet IP54 for common dry factory floor environment is suitable.
Maintain spacing from:
enclosure walls
wireways
adjacent equipment
Allow a minimum of 20 mm clearance on all sides. This provides ventilation and galvanic
isolation.
PLC enclosure
System assembly, construction and connection
AC500 (Standard) > Mechanical dimensions
2022/01/313ADR010278, 3, en_US976