It is recommended to mount the modules on an grounded mounting plate, or an grounded DIN
rail, independent of the mounting location.
Fig. 181: Installation of AC500/S500 modules in a switchgear cabinet
1 Cable duct
2 Distance from cable duct ≥20 mm
3 Mounting plate, grounded
NOTICE!
Horizontal mounting is highly recommended.
Vertical mounting is possible, however, derating consideration should be made
to avoid problems with poor air circulation and overheating (see
Ä
Chapter
2.6.1.1 “Environmental conditions” on page 971).
System assembly, construction and connection
AC500 (Standard) > Mechanical dimensions