Parameter Value
Unused inputs Must be configured as "unused".
Overvoltage protection Yes
Technical data of the analog inputs, if used as digital inputs
Parameter Value
Number of channels per module Max. 8
Distribution of channels into groups 1 group of 8 channels
Connections of the channels C0+ to C7+ Terminals 3.0 to 3.7
Reference potential for the inputs Terminals 1.9 to 4.9 (ZP)
Input signal delay Typ. 8 ms, configurable from 0.1 to 32 ms
Indication of the input signals 1 LED per channel
Input signal voltage 24 VDC
Signal 0 -30 V...+5 V
Undefined signal +5 V...+13 V
Signal 1 +13 V...+30 V
Input current per channel
Input voltage +24 V Typ. 7 mA
Input voltage +5 V Typ. 1.4 mA
Input voltage +15 V Typ. 4.3 mA
Input voltage +30 V < 9 mA
Input resistance Ca. 3.5 kW
Technical data of the analog outputs
Parameter Value
Number of channels per module 8, all channels for voltage, the first 4 channels
also for current
Distribution of channels into groups 1 group of 8 channels
Channels C0-...C7- Terminals 2.0...2.7
Channels C0+...C7+ Terminals 3.0...3.7
Output type Bipolar with voltage, unipolar with current
Galvanic isolation Against internal supply and other modules
Configurability -10 V...+10 V, 0 mA...20 mA, 4 mA...20 mA
(each output can be configured individually),
current outputs only channels 0...3
Output resistance (load), as current output 0 W...500 W
Output loadability, as voltage output Max. ±10 mA
Indication of the output signals One LED per channel
Resolution 12 bits (+ sign)
I/O modules > Analog I/O modules
2022/01/313ADR010278, 3, en_US430