EasyManua.ls Logo

ABB AC500 V3 - Connection of active-type analog sensors (Voltage) with no galvanically isolated power supply

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The function of the LEDs is described under Diagnosis and displays / displays
Ä
Chapter
1.6.2.2.3.7 “Diagnosis” on page 475.
In order to avoid error messages or long processing times, it is useful to configure unused
analog input channels as "unused".
Connection of active-type analog sensors (Voltage) with no galvanically isolated power supply
Fig. 36: Connection example
CAUTION!
If GND is not directly connected to ZP at the sensor, the supply current flows
via the GND line to ZP. Measuring errors can only occur caused by voltage
differences higher than ±20 V DC between GND and ZP.
The measuring ranges can be configured
Ä
Chapter 1.6.2.2.3.6 “Parameterization”
on page 472 :
Voltage -50 mV...+50 mV 1 channel used
Voltage -500 mV...+500 mV 1 channel used
Voltage -1 V...+1 V 1 channel used
Voltage -5 V...+5 V 1 channel used
Voltage -10 V...+10 V 1 channel used
Voltage 0 V...+5 V 1 channel used
Voltage 0 V...+10 V 1 channel used
Standard ranges
Device specifications
I/O modules > Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 459

Table of Contents

Other manuals for ABB AC500 V3

Related product manuals