The following measuring ranges can be configured
Ä
Chapter 1.6.2.2.2.6 “Parameterization”
on page 444
Ä
Chapter 1.6.2.2.2.9 “Measuring ranges” on page 449:
Voltage 0 V...10 V with differential inputs, 2 chan-
nels used
Voltage -10 V...+10 V with differential inputs, 2 chan-
nels used
The function of the LEDs is described under Displays
Ä
Chapter 1.6.2.2.2.7 “Diagnosis”
on page 447.
In order to avoid error messages or long processing times, it is useful to configure unused
analog input channels as "unused".
Use of analog inputs as digital inputs
Several (or all) analog inputs can be configured as digital inputs. The inputs are not galvanically
isolated against the other analog channels.
1.0
I0-
1.1
I1-
1.8
UP
1.9
ZP
PTC
2.0
I0+
2.1
I1+
2.8
UP
2.9
ZP
UP
ZP
Fig. 32: Connection example
The following operating mode can be configured
Ä
Chapter 1.6.2.2.2.6 “Parameterization”
on page 444
Ä
Chapter 1.6.2.2.2.9 “Measuring ranges” on page 449
Digital input 24 V 1 channel used
Effect of incorrect input ter-
minal connection
Wrong or no signal detected,
no damage up to 35 V
The function of the LEDs is described under Displays.
Internal data exchange
Digital inputs (bytes) 0
Digital outputs (bytes) 0
Counter input data (words) 16
Counter output data (words) 0
I/O modules > Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 443