Technical data of the PTO outputs
Parameter PM5012-T-ETH PM5012-R-ETH PM5032-T-ETH
PM5052-T-ETH
PM5072-
T-2ETH
PM5032-R-
ETH
PM5052-R-
ETH
PTO
Useable outputs - - 4 1
pair of output
Fast output,
max. 100 kHz
- - DO4 … DO7
For 2 PTO 200
kHz *) Pulse/
Direction or
CC/Ccw modes
as pair of out-
puts
DC12 … DC13
DO4 … DO7
as 4 PTO 100
kHz Pulse out-
puts / Direction
using fast
output 5kHz
DO0...DO3
*) If the load is less than 100 mA it is strongly recommended to connect an additional load
resistor (240 Ω/5 W or 270 Ω/5 W) to the output to improve the pulse signal.
Technical data of the PWM outputs
Parameter PM5012-T-ETH PM5012-R-ETH PM5032-T-ETH
PM5052-T-ETH
PM5072-
T-2ETH
PM5032-R-
ETH
PM5052-R-
ETH
PWM
Useable outputs 4 - 8 2
Fast output
max. 5 kHz
DO0 ... DO3 - DO0 … DO3 -
Fast output,
max. 100 kHz
- - DO4 … DO7 DC12 … DC13
Device specifications