Parameter Value
Unused voltage inputs Are configured as "unused"
Unused current inputs Have a low resistance, can be left open-circuited
Overvoltage protection Yes
Technical data of the analog inputs, if used as digital inputs
Parameter Value
Number of channels per module Max. 4
Distribution of channels into groups 1 group of 4 channels
Connections of the channels I0+ to I3+ Terminals 2.0 to 2.3
Reference potential for the inputs Terminals 1.9, 2.9, 3.9 and 4.9 (ZP)
Input signal delay Typ. 8 ms, configurable from 0.1 to 32 ms
Indication of the input signals 1 LED per channel
Input signal voltage 24 V DC
Signal 0 -30 V...+5 V
Undefined signal +5 V...+13 V
Signal 1 +13 V...+30 V
Input current per channel
Input voltage +24 V Typ. 7 mA
Input voltage +5 V Typ. 1.4 mA
Input voltage +15 V Typ. 4.3 mA
Input voltage +30 V < 9 mA
Input resistance ca. 3.5 kW
Technical data of the analog outputs
Parameter Value
Number of channels per module 4, all channels for voltage and current
Distribution of channels into groups 1 group of 4 channels
Channels O0-...O3- Terminals 3.0...3.3
Channels O0+...O3+ Terminals 4.0...4.3
Output type Bipolar with voltage, unipolar with current
Galvanic isolation Against internal supply and other modules
Configurability -10 V...+10 V, 0 mA...20 mA, 4 mA...20 mA (each
output can be configured individually), current out-
puts only channels 0...3
Output resistance (load), as current
output
0 W...500 W
Output loadability, as voltage output Max. ±10 mA
Indication of the output signals One LED per channel
Resolution 12 bits (+ sign)
I/O modules > Analog I/O modules
2022/01/313ADR010278, 3, en_US522