Parameter Value
Input signal range 0 V AC...265 V AC
Input signal frequency 47 Hz...63 Hz
Input characteristic According EN 61132-2 Type 2
Signal 0 0 V AC...40 V AC
Undefined signal > 40 V AC...< 74 V AC
Signal 1 74 V AC...265 V AC
Input current per channel
Input voltage = 159 V AC > 7 mA
Input voltage = 40 V AC < 5 mA
Overvoltage protection Yes
Max. cable length
Shielded 1000 m
Unshielded 600 m
Technical data of the relay outputs
Parameter Value
Number of channels per module 4 relay outputs
Distribution of channels into groups 4 groups of 1 channel each
Connection of the four relays
Ä
Chapter 1.6.1.2.8.3 “Connections”
on page 340
Galvanic isolation Between the channels and from the rest of the
module
Indication of the output signals 1 yellow LED per channel, the LED is ON when
the relay coil is energized
Monitoring point of output indicator LED is controlled by process CPU
Way of operation Non-latching type
Output delay (0->1 or 1->0) On request
Relay power supply By UP process supply voltage
Relay outputs
Output short circuit protection Must be provided externally with a fuse or cir-
cuit breaker
Rated protection fuse 6 A gL/gG per channel
Output switching capacity
Resistive load, max. 3 A; 3 A (230 V AC), 2 A (24 V DC)
Inductive load, max. 1.5 A; 1.5 A (230 V AC), 1.5 A (24 V DC)
Lamp load 60 W (230 V AC), 10 W (24 V DC)
Lifetime (cycles) Mechanical: 300 000;
Under load: 300 000 (24 V DC at 2 A), 200 000
(120 V AC at 2 A), 100 000 (230 V AC at 3 A)
Spark suppression with inductive AC load Must be performed externally according to
driven load specifications