The following measuring ranges can be configured
Ä
Chapter 1.7.5.2.7 “Parameterization”
on page 815
Ä
Chapter 1.7.5.2.9.1 “Input ranges voltage, current and digital input”
on page 828:
Pt100 -50 °C...+400 °C 2-wire configuration, 1
channel used
Pt1000 -50 °C...+400 °C 2-wire configuration, 1
channel used
Ni1000 -50 °C...+150 °C 2-wire configuration, 1
channel used
The function of the LEDs is described under Diagnosis and displays / Displays
Ä
Chapter
1.7.5.2.8 “Diagnosis and state LEDs” on page 821.
The module CI501-PNIO performs a linearization of the resistance characteristic.
To avoid error messages from unused analog input channels, configure them as "unused".
Connection of resistance thermometers in 3-wire configuration to the analog inputs
When resistance thermometers (Pt100, Pt1000, Ni1000) are used, a constant current must
flow through them to build the necessary voltage drop for the evaluation. For this, the module
CI501-PNIO provides a constant current source which is multiplexed over the max. 4 analog
input channels.
The following figure shows the connection of resistance thermometers in 3-wire configuration to
the analog inputs AI0 and AI1. Proceed with the analog inputs AI2 and AI3 in the same way.
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/313ADR010278, 3, en_US804