ABB AC500 V3 - 2.6.4.4 Connection of wires at the spring terminals

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Type Front terminal
Degree of protection IP 20
Stripped conductor end 9 mm, min. 8 mm
Needed tool Slotted screwdriver
Dimensions 2.5 x 0.4 to 3.5 x 0.5 mm, screwdriver must be at least 15 mm
free of insulation at the tip
Number of cores per terminal Conductor type Cross section
1 Solid 0.08 mm² to 2.5 mm²
1 Flexible 0.08 mm² to 2.5 mm²
1 with wire-end ferrule Flexible 0.25 mm² to 1.5 mm²
2 Solid Not intended
2 Flexible Not intended
2 with TWIN wire end ferrule (length
10 mm) with plastic sleeve
Flexible 2 x 0.25 mm² or 2 x 0.5 mm² or
2 x 0.75 mm², with square cross-
section of the wire-end ferrule also
2 x 1.0 mm²
2.6.4.4 Connection of wires at the spring terminals
1 2 3
b
a
conductor driver
screw-
b
Screwdriver
for
Opening forOpening
closed
Terminal
open
Terminal
a
inserted
Screwdriver
Screwdriver
Spring
Fig. 190: Connect the wire to the spring terminal (steps 1 to 3)
Connection
System assembly, construction and connection
AC500 (Standard) > Connection and wiring
2022/01/313ADR010278, 3, en_US992