EasyManua.ls Logo

ABB AC500 V3 - Channel parameters for the analog inputs (4 x)

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Channel parameters for the analog inputs (4x)
Name Value Internal value Internal
value, type
Default EDS Slot /
Index
Input 0,
Channel con-
figuration
see
Ä
Table 125 “
Channel con-
figuration”
on page 601
see
Ä
Table 125 “
Channel con-
figuration”
on page 601
BYTE 0 0x0Y09
Input 0,
Check
channel
see
Ä
Table 126 “
Channel mon-
itoring”
on page 602
see
Ä
Table 126 “
Channel mon-
itoring”
on page 602
BYTE 0 0x0Y0A
: : : : :
: : : : :
Input 3,
Channel con-
figuration
see
Ä
Table 125 “
Channel con-
figuration”
on page 601
see
Ä
Table 125 “
Channel con-
figuration”
on page 601
BYTE 0 0x0Y0F
Input 3,
Check
channel
see
Ä
Table 126 “
Channel mon-
itoring”
on page 602
see
Ä
Table 126 “
Channel mon-
itoring”
on page 602
BYTE 0 0x0Y10
Table 125: Channel configuration
Internal value Operating modes of the analog inputs, individually configu-
rable
0 (default) Not used
1 0 V...10 V
2 Digital input
3 0 mA...20 mA
4 4 mA...20 mA
5 -10 V...+10 V
8 2-wire Pt100 -50 °C...+400 °C
9 3-wire Pt100 -50 °C...+400 °C *)
10 0 V...10 V (voltage diff.) *)
11 -10 V...+10 V (voltage diff.) *)
14 2-wire Pt100 -50 °C...+70 °C
15 3-wire Pt100 -50 °C...+70 °C *)
16 2-wire Pt1000 -50 °C...+400 °C
17 3-wire Pt1000 -50 °C...+400 °C *)
18 2-wire Ni1000 -50 °C...+150 °C