EasyManua.ls Logo

ABB AC500 V3 - Technical data of the digital outputs

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Process supply voltage
Connections Terminals 1.8, 2.8, 3.8 and 4.8 for UP (+24
V DC) and 1.9, 2.9, 3.9 and 4.9 for ZP (0
V)
Protection against reverse voltage yes
Rated protection fuse at UP 10 A fast
Rated value 24 V DC
Max. ripple 5 %
Current consumption
From UP 0.07 A + max. 0.5 A per output
From 24 V DC power supply at the termi-
nals UP/L+ and ZP/M of the CPU/communi-
cation interface module
ca. 2 mA
Inrush current from UP (at power-up)
0.04 A
2
s
Galvanic isolation Yes, per module
Max. power dissipation within the module 6 W (outputs unloaded)
Weight (without terminal unit) ca. 125 g
Mounting position Horizontal mounting or vertical with
derating (output load reduced to 50% at 40
°C)
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in
the switchgear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
Technical data of the digital outputs
Parameter Value
Number of channels per module 16 outputs (with transistors)
Distribution of the channels into groups 1 group of 16 channels
Connection of the channels
DO0 to DO7 Terminals 1.0 to 1.7
DO8 to DO15 Terminals 2.0 to 2.7
Device specifications
I/O modules > Digital/Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 609