EasyManua.ls Logo

ABB AC500 V3 - Technical data of the digital inputs;outputs if used as inputs; Technical data of the digital inputs;outputs if used as outputs

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data of the digital inputs/outputs if used as inputs
Parameter Value
Number of channels per module Max. 16 digital inputs
Reference potential for all inputs Terminals 1.9, 2.9, 3.9 and 4.9 (negative pole of
the process supply voltage, signal name ZP)
Input current, per channel See Technical Data of the Digital Inputs
Ä
Chapter 1.6.1.2.3.8.1 “Technical data of the
digital inputs” on page 298
Input type acc. to EN 61131-2 Type 1
Input delay (0->1 or 1->0) Typ. 8 ms, configurable from 0.1 to 32 ms
Input signal voltage 24 V DC
Signal 0 -3 V...+5 V *)
undefined signal > +5 V...< +15 V
Signal 1 +15 V...+30 V
Ripple with signal 0 Within -3 V...+5 V *)
Ripple with signal 1 Within +15 V...+30 V
Max. cable length
Shielded 1000 m
Unshielded 600 m
*) Due to the direct connection to the output, the demagnetizing varistor is also effective at the
input (see figure) above. This is why the difference between UPx and the input signal must not
exceed the clamp voltage of the varistor. The varistor limits the clamp voltage to approx. 36 V.
Consequently, the input voltage must range from -12 V to +30 V when UPx = 24 V and from
-6 V to +30 V when UPx = 30 V.
Technical data of the digital inputs/outputs if used as outputs
Parameter Value
Number of channels per module Max. 16 transistor outputs
Reference potential for all outputs Terminals 1.9, 2.9, 3.9 and 4.9 (negative pole
of the process supply voltage, signal name ZP)
Common power supply voltage For all outputs: terminals 1.8, 2.8, 3.8 and 4.8
(positive pole of the process supply voltage,
signal name UP)
Output voltage for signal 1 UP (-0.8 V)
Output delay (0->1 or 1->0) On request
Output current
Rated value, per channel 500 mA at UP = 24 V
Maximum value (all channels together) 8 A
Leakage current with signal 0 < 0.5 mA
Rated protection fuse on UP 10 A fast
Demagnetization when inductive loads are
switched off
With varistors integrated in the module (see
figure below)
Switching frequency
With resistive load On request
Device specifications
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US300

Table of Contents

Other manuals for ABB AC500 V3

Related product manuals