EasyManua.ls Logo

ABB AC500 V3 - Ordering data

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Indication of the output signals 1 yellow LED per channel; the LED is on when
the output signal is high (signal 1) and the
module is powered via the I/O bus
Way of operation Non-latching type
Min. output voltage at signal 1 UP -0.3 V at max. current consumption
Output delay (max. at rated load)
0 to 1 50 µs
1 to 0 200 µs
Output data length 2 bytes
Output current
Rated current per channel (max.) 0.5 A at UP 24 V DC
Rated current per group (max.) 8 A
Lamp load (max.) 5 W
Max. leakage current with signal 0 0.5 mA
Output type Non-protected
Protection type External fuse on each channel
Rated protection fuse (for each channel) 3 A fast
Demagnetization when inductive loads are
switched off
Must be performed externally according to driven
load specification
Switching Frequencies
With inductive loads Max. 0.5 Hz
With lamp loads Max. 11 Hz at max. 5 W
Short-circuit-proof / Overload-proof No
Overload message No
Output current limitation No
Resistance to feedback against 24 V
DC
No
Connection of 2 outputs in parallel Not possible
Max. cable length
Shielded 500 m
Unshielded 150 m
Ordering data
Part no. Description Product life cycle phase *)
1SAP 230 900 R0000 DO562, digital output module, 16 DO,
transistor output
Active
1TNE 968 901 R3101 Terminal block TA563-9, 9 pins, screw
front, cable side, 6 pieces per unit
Active
1TNE 968 901 R3102 Terminal block TA563-11, 11 pins,
screw front, cable side, 6 pieces per
unit
Active
Device specifications
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US210