Internal data exchange
Without the fast counter With the fast counter (only
with AC500)
Digital inputs (bytes) 3 5
Digital outputs (bytes) 3 5
Counter input data (words) 0 4
Counter output data (words) 0 8
I/O configuration
The module itself does not store configuration data. It receives its parameterization data from
the master device of the I/O bus (CPU or communication interface module) during power-up of
the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Parameterization
Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module: Module slot address: Y = 1...10
Name Value Internal
value
Internal
value,
type
Default Min. Max. EDS Slot/
Index
Module ID Internal 1215
1
)
Word 1215
0x04BF
0 65535 0x0Y01
Ignore
module
2
)
No
Yes
0
1
Byte No
0x00
Not for
FBP
Parameter
length
Internal 9 Byte 9-CPU
8-FBP
0 255 0x0Y02
Check
supply
Off
on
0
1
Byte On
0x01
0 1 0x=Y03
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US284