Parameter Value
Way of operation Non-latching type
Max. output voltage at signal 1 20 V DC at max. current consumption
Output delay
0 to 1 50 µs
1 to 0 200 µs
Output data length 1 byte
Output current
Rated current per channel (max.) 0.5 A at UP 24 V DC
Rated current per group (max.) 4 A
Rated current (all channels together,
max.)
4 A
Lamp load (max.) 5 W
Max. leakage current with signal 0 0.5 mA
Output type Non-protected
Protection type External fuse on each channel
Rated protection fuse (for each channel) 3 A fast
Demagnetization when inductive loads are
switched off
Must be performed externally according to
driven load specification
Switching Frequencies
With inductive loads Max. 0.5 Hz
With lamp loads Max. 11 Hz at max. 5 W
Short-circuit-proof / Overload-proof No
Overload message No
Output current limitation No
Resistance to feedback against 24 V DC No
Connection of 2 outputs in parallel Not possible
Max. cable length
Shielded 500 m
Unshielded 150 m
Ordering data
Part no. Description Product life cycle phase *)
1TNE 968 902 R2301 DX561, digital input/output module,
8 DI 24 V DC, 8 DO 24 V DC,
transistor output
Active
1TNE 968 901 R3101 Terminal block TA563-9, 9 pins, screw
front, cable side, 6 pieces per unit
Active
1TNE 968 901 R3102 Terminal block TA563-11, 11 pins,
screw front, cable side, 6 pieces per
unit
Active
1TNE 968 901 R3103 Terminal block TA564-9, 9 pins, screw
front, cable front, 6 pieces per unit
Active
Device specifications
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US254