Parameter Value
Rated current (all channels together,
max.)
1.6 A
Lamp load (max.) Not applicable
Max. leakage current with signal 0 < 0.5 mA
Output type Non-protected
Protection type External fuse on each channel
Rated protection fuse (for each channel) 1 A fast
Demagnetization when inductive loads are
switched off
Must be performed externally according to
load specification
Switching frequency
With inductive loads Max. 0.5 Hz
Short-circuit-proof / overload-proof No
Overload message No
Output current limitation No
Resistance to feedback against 24 V DC
signals
Yes
Connection of 2 outputs in parallel Not possible
Max. cable length
Shielded 500 m
Unshielded 150 m
Ordering data
Part no. Description Product life cycle phase *)
1TNE 968 902 R2001 DC561, digital input/output module,
16 configurable inputs/outputs,
transistor output, interfast connector
Classic
*) Modules in lifecycle Classic are available from stock but not recommended
for planning and commissioning of new installations.
1.6.1.1.2 DC562 - Digital input/output module
● 16 configurable digital inputs/outputs in 1 group, 24 V DC
● Module-wise galvanically isolated
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US150