The TA566 is snapped into the back side of the device's housing
Ä
“Mounting I/O modules on a
metal plate” on page 940.
Parameter Value
Weight 5 g
Dimensions 29 mm x 28 mm x 5 mm
Part no. Description Product life cycle phase *)
1TNE 968 901 R3107 TA566, wall mounting acces-
sory, 100 pieces
Active
*) Modules in lifecycle Classic are available from stock but not recommended
for planning and commissioning of new installations.
2.6 AC500 (Standard)
2.6.1 System data AC500
2.6.1.1 Environmental conditions
Table 196: Process and supply voltages
Parameter Value
24 V DC
Voltage 24 V (-15 %, +20 %)
Protection against reverse polarity Yes
120 V AC
Voltage 120 V (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
230 V AC
Voltage 230 V AC (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
120 V AC...240 V AC wide-range supply
Voltage 120 V...240 V (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
Allowed interruptions of power supply, according to EN 61131-2
DC supply Interruption < 10 ms, time between 2 interrup-
tions > 1 s, PS2
AC supply Interruption < 0.5 periods, time between 2
interruptions > 1 s
NOTICE!
Exceeding the maximum power supply voltage for process or supply voltages
could lead to unrecoverable damage of the system. The system might be
destroyed.
Handling
instruction
Technical data
Ordering data
System assembly, construction and connection
AC500 (Standard) > System data AC500
2022/01/31 3ADR010278, 3, en_US 971