The inputs/outputs are galvanically isolated from the CANopen network. There is no potential
separation between the channels. The configuration of the analog inputs/outputs is performed
by software.
For use in extreme ambient conditions (e.g. wider temperature and humidity range), a special
XC version of the device is available.
1.7.2.2.2 Functionality
Parameter Value
Interface CAN
Protocol CANopen
Power supply From the process supply voltage UP
Supply of the electronic circuitry of the I/O
modules attached
Through the I/O bus interface (I/O bus)
Rotary switches For setting the CANopen Node ID for configura-
tion purposes (00h to FFh)
LED displays For system displays, signal states, errors and
power supply
External supply voltage Via terminals ZP, UP and UP3 (process supply
voltage 24 V DC)
Transmission rates 10 / 20 / 50 / 125 / 250 / 500 / 800 kbit/s 1
Mbit/s Auto transmission rate detection is sup-
ported
Bus connection Depending on used terminal unit TU510: 9-pin
D-sub connector TU518: 10-pin terminal block
Processor Hilscher NETX 100
Expandability CI58x can only be used on onboard CAN inter-
face and without any I/O expansion module
Ä
Table 132 “CANopen” on page 617.
State display Module state: PWR/RUN, CN-RUN, CN-ERR,
E-ERR, I/O bus
Adjusting elements 2 rotary switches for generation of the node
address
Ambient temperature
System data AC500
Ä
Chapter 2.6.1 “System
data AC500” on page 971
System data AC500 XC
Ä
Chapter 2.7.1
“System data AC500-XC” on page 1023
Current consumption UP: 0.2 A UP3: 0.06 A + 0.5 A max. per output
Weight (without terminal unit) Ca. 125 g
Process supply voltages UP/UP3
Rated value 24 V DC (for inputs and outputs)
Max. load for the terminals 10 A
Protection against reversed voltage Yes
Rated protection fuse on UP/UP3 10 A fast
Galvanic isolation CANopen interface against the rest of the
module
Inrush current from UP (at power up) On request
Device specifications
Communication interface modules (S500) > CANopen
2022/01/31 3ADR010278, 3, en_US 621